Place of Origin:
China
Brand Name:
G-Tech
Certification:
ISO, CE, ROHS
Model Number:
Tower UPS
10KVA Online UPS Uninterruptible Power Supply High Frequency
3/3 Three Phases input Three Phases Output 3:3
This series of UPS applies CPU integrated control technology, which allows UPS to response promptly and accurately when power outage, high or low voltage, surge, transient or spike occurs so on. It possesses automatic startup function, automatic voltage regulation function and a wide range of input voltage, so it is applicable to all kind of electric power environment. In addition, its design is humanized and elegant with LED or LCD display, those are two alternatives.
Production Introduction
This series UPS applies CPU intergrated control technology, which allows UPS to response prometly and accurately when power outage, high or low voltage, surge, transient or spike occurs while its protection port provides protection for special external devices, such as printers and so on. It possess automatic startup function,automatic voltage regulation function and a wide range of input voltage, so it is applicable to all kinds
of electric power environment. In addition, its design is humanized and elegant with LED or LCD display, those are tow alternatives.
MODEL |
PT33-20KS |
PT33-30KS |
PT33-40KS |
PT33-60KS |
PT33-80KS |
||||
Rated power |
20KVA/20KW |
30KVA/30KW |
40KVA/36KW |
60KVA/60KW |
80KVA/80KW |
||||
INPUT |
|||||||||
Input Mode |
Three phases + N + G |
||||||||
Rated Voltage |
380/400/415Vac |
||||||||
Voltage Range |
208~478Vac |
||||||||
Frequency |
45-55Hz at 50Hz/54-66Hz at 60Hz (Adaptive) |
||||||||
Range Power Factor |
≥ 0.99 |
||||||||
Harmonic Current Distortion (THDi) |
≤ 3%(100% nonlinear load ) |
||||||||
Bypass Frequency Range |
Upper limit of bypass protection voltage: 220V:﹢ 25%(﹢ 10%,﹢ 15%,﹢ 20% optional); 230V:﹢ 20%(﹢ 10%,﹢ 15% optional); 240V:﹢ 15%(﹢ 10% optional) |
||||||||
Minimum bypass protection voltage: -45%( -20%,-30% optional) |
|||||||||
Bypass frequency protection range: ±10% |
|||||||||
OUTPUT |
|||||||||
Input Mode |
Three phases + G or Single phase + N |
||||||||
Rated Voltage |
380/400/415Vac or 220/230/240Vac |
||||||||
Range Power Factor |
0.8 |
||||||||
Regulation Accuracy |
±1% |
||||||||
Output Frequency |
AC mode |
±1%,±2%,±4%,±5%,±10% settable (50/60±0.2)Hz |
|||||||
Battery mode |
(50/60±0.2%) Hz |
||||||||
Load Peak Ratio |
3:1 |
||||||||
Output Voltage Distortion |
≤ 2% with linear load |
||||||||
≤ 5% nonlinear load |
|||||||||
BATTERY |
|||||||||
Battery Voltage |
DC±192V/±204/±216V/±228/±240V (±16/17/18/19/20 pcs ) optional |
||||||||
Charge Current |
10A max |
||||||||
OTHERS |
|||||||||
Transfer time |
AC mode to bypass mode: 0ms(following); AC mode to battery mode: 0ms |
||||||||
Efficiency |
Normal mode≥ 94.5% |
||||||||
Communication Interface |
USB,RS485, dry contact , parallel connection(optional), SNMP card(optional), relay card(optional) |
||||||||
Standard |
YD/T1095-2008 |
||||||||
PROTECTION |
|||||||||
Overload |
Normal mode: load ≤ 110%,60min; ≤ 125%, 10 mins; ≤ 150%, 1min; ≥ 150% shutdown immediately
|
||||||||
Over heat Protection |
Normal mode: switch to bypass mode; Battery mode: turn off the output immediately |
||||||||
Emergency Power Off(EPO) |
Shutdown the output immediately |
||||||||
ENVIRONMENT |
|||||||||
Operating Temperature |
0℃~ 40℃ |
||||||||
Storage Temperature |
-25℃~ 55℃ |
||||||||
Relative Humidity |
0 ~ 95% no condensation |
||||||||
Altitude |
< 1500m,In case of exceeding 1500m, it shall be reduced according to GB/T 3859.2 |
||||||||
PHYSCIAL |
|||||||||
Dimension W * D * H(mm) |
724X250X534 |
724X301X961 |
|||||||
Net Weight(kg) |
45 |
46 |
48 |
80.5 |
82.5 |
Feature of G Tech UPS
1) LCD display, large blue interface in English, user-friendly(Panel Display: UPS status, input/output voltage and frequency, battery voltage, capacity, load temperature, history recods, adjust voltage, ECO mode)
2) Rack-Tower convertible
3) With ECO can be highly efficient energy-saving, reducing user costs
4) Double-conversion online design, so that the output of the frequency UPS tracking, lock-in voltage regulator,
filter noise low distortion, without interfering with the pure sine wave power supply fluctuations.
5) Advanced Digital Signal Processing (DSP) microprocessor technology to ensure the consistency and reliability of UPS.
6) With battery hot-swapping function
Send your inquiry directly to us