How to calculate the battery solution for the UPS

March 3, 2026
Latest company news about How to calculate the battery solution for the UPS
For Example:
3KVA UPS 3000W backup 30min :
1.KVA*PFC=O/P P
3000*0.7=2100W(You can find this
on the catalogue capacity column)
1. Output P/DC=I
2100W/ 96VDC=21.875(You can find
the DC on the battery voltage column on the catalogue)
2. I/C=AH
21.875/0.92=23.77AH(You can check
the battery C on the bellow diagram)
So must 8pcs 12V/24AH battery.
 
This is on the full load mode. If you can use 30minutes on the
full load then on the half load can use about 60minutes.
latest company news about How to calculate the battery solution for the UPS  0
Note:1.the first row is the backup time
2.The second row is the battery C
Calculate formula
KVA*PFC/VDC/Batter C=AH